• DocumentCode
    2036950
  • Title

    Central degassing - when does it bang

  • Author

    Kölbel, Dieter

  • Author_Institution
    EXIDE Technol. Ind. Energy
  • fYear
    2005
  • fDate
    Sept. 2005
  • Firstpage
    223
  • Lastpage
    226
  • Abstract
    Battery suppliers have answered the demands of their customers for less ventilation for equipment cabinets where batteries are included with solutions for central degassing on the VRLA-Batteries. From several intelec´s we have reports that the majority of hydrogen and oxygen produced by VRLA-Batteries is lost through the case walls instead through the vents. Quantities are rarely reported and difficult to calculate The scope of this paper is to show how much hydrogen is escaping through the container wall of VRLA batteries with central degassing as an option and when the concentration of hydrogen will reach an explosive level.
  • Keywords
    hydrogen economy; lead acid batteries; VRLA-batteries; battery suppliers; equipment cabinet ventilation; hydrogen production; oxygen production; Battery charge measurement; Charge measurement; Containers; Current measurement; Hydrogen; Temperature; Testing; Time measurement; Voltage; Welding;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Conference, 2005. INTELEC '05. Twenty-Seventh International
  • Conference_Location
    Estrel Hotel, Berlin, Germany
  • Print_ISBN
    978-3-8007-2905-0
  • Type

    conf

  • DOI
    10.1109/INTLEC.2005.335096
  • Filename
    4134335