Abstract
In oil-immersed power transformers, an insulating oil/pressboard (PB) composite insulation system is generally applied. In the system, charges accumulate at the oil/PB interface and electric field distribution changes depending on time and oil condition. In this paper, the authors directly measured the DC electric field in oil/PB composite insulation system using Kerr electro-optic field measurement. From the results, they proposed the charge behavior model. They calculated the electric field distribution using the finite element method (FEM), taking account of measured charge behavior. Finally, they confirmed that the charge model explains the experimental results well, including in the case of the polarity reversals.
Keywords
Kerr electro-optical effect; composite insulating materials; electric field measurement; fibre optic sensors; finite element analysis; insulation testing; power transformer insulation; power transformer testing; transformer oil; DC electric field measurement; Kerr electro-optic field measurement; charge behavior model; electric field distribution; finite element method; insulating oil/pressboard composite insulation system; oil-immersed power transformers; polarity reversals; Charge measurement; Current measurement; Dielectrics and electrical insulation; Electric variables measurement; Finite element methods; Kerr effect; Oil insulation; Petroleum; Power transformer insulation; Power transformers;
fLanguage
English
Publisher
ieee
Conference_Titel
Dielectric Liquids, 2002. ICDL 2002. Proceedings of 2002 IEEE 14th International Conference on
Print_ISBN
0-7803-7350-2
Type
conf
DOI
10.1109/ICDL.2002.1022752
Filename
1022752
Link To Document