    A new protection criterion for high-voltage transmission line using two-end voltage transients

  • Author

    Xia, M.C. ; Huang, Y.Z.

  • Author_Institution
    Tsinghua Univ., Beijing, China
  • Volume
    1
  • fYear
    2004
  • fDate
    5-8 April 2004
  • Firstpage
    84
  • Abstract
    A new transient based protection criterion for high voltage transmission line based on the wavelet transform results of voltage transient signals at the two ends of the line is presented. The difference of high frequency voltage transients at the two ends of the transmission line when in-zone faulted and out-zone faulted is analyzed, and the transient voltage content ratio and transient voltage singularity ratio are deduced. Two-end transient voltage protection criterion using the transient voltage singularity ratio is proposed, and the principles of the protection settings are given. The calculation of transient voltage content ratio and transient voltage singularity ratio using wavelet transform is deduced. Simulations of different fault locations and different fault types are carried out for testing and analyzing the protection criterion.
  • Keywords
    power transmission faults; power transmission protection; transients; transmission line theory; wavelet transforms; fault locations; fault types; high-voltage transmission lines; in-zone faulted; out-zone faulted; power transmission faults; power transmission protection; protection criterion; transient voltage content ratio; transient voltage signals; transient voltage singularity ratio; transmission line theory; two-end voltage transients; wavelet transform;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2004. Eighth IEE International Conference on
  • ISSN
    0537-9989
  • Print_ISBN
    0-86341-385-4
  • Type

    conf

  • DOI
    10.1049/cp:20040069
  • Filename
    1364812