DocumentCode
2045555
Title
New algorithm for generator differential protection
Author
Kasztenny, B. ; Finney, D.
Author_Institution
Gen. Electr. Multilin, Canada
Volume
1
fYear
2004
fDate
5-8 April 2004
Firstpage
144
Abstract
A new algorithm for stator differential protection is presented. The algorithm addresses extreme cases of current transformer saturation, including both AC saturation under large currents and DC saturation under small but DC offset currents. While ensuring good sensitivity and excellent security, the trip time of the actual relay hardware implementing the presented algorithm is below one power cycle.
Keywords
current transformers; differential detection; electric generators; relay protection; stators; AC saturation; DC saturation; current transformer saturation; generator differential protection; relay protection; relay security; relay sensitivity; stator differential protection; trip time;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, 2004. Eighth IEE International Conference on
ISSN
0537-9989
Print_ISBN
0-86341-385-4
Type
conf
DOI
10.1049/cp:20040084