Title :
New algorithm for generator differential protection
Author :
Kasztenny, B. ; Finney, D.
Author_Institution :
Gen. Electr. Multilin, Canada
Abstract :
A new algorithm for stator differential protection is presented. The algorithm addresses extreme cases of current transformer saturation, including both AC saturation under large currents and DC saturation under small but DC offset currents. While ensuring good sensitivity and excellent security, the trip time of the actual relay hardware implementing the presented algorithm is below one power cycle.
Keywords :
current transformers; differential detection; electric generators; relay protection; stators; AC saturation; DC saturation; current transformer saturation; generator differential protection; relay protection; relay security; relay sensitivity; stator differential protection; trip time;
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
Print_ISBN :
0-86341-385-4
DOI :
10.1049/cp:20040084