• DocumentCode
    2045555
  • Title

    New algorithm for generator differential protection

  • Author

    Kasztenny, B. ; Finney, D.

  • Author_Institution
    Gen. Electr. Multilin, Canada
  • Volume
    1
  • fYear
    2004
  • fDate
    5-8 April 2004
  • Firstpage
    144
  • Abstract
    A new algorithm for stator differential protection is presented. The algorithm addresses extreme cases of current transformer saturation, including both AC saturation under large currents and DC saturation under small but DC offset currents. While ensuring good sensitivity and excellent security, the trip time of the actual relay hardware implementing the presented algorithm is below one power cycle.
  • Keywords
    current transformers; differential detection; electric generators; relay protection; stators; AC saturation; DC saturation; current transformer saturation; generator differential protection; relay protection; relay security; relay sensitivity; stator differential protection; trip time;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2004. Eighth IEE International Conference on
  • ISSN
    0537-9989
  • Print_ISBN
    0-86341-385-4
  • Type

    conf

  • DOI
    10.1049/cp:20040084
  • Filename
    1364827