Title :
Power transformer monitoring using UHF sensors: installation and testing
Author :
Judd, M.D. ; Farish, O. ; Pearson, J.S. ; Breckenridge, T. ; Pryor, B.M.
Author_Institution :
Centre for Electr. Power Eng., Strathclyde Univ., Glasgow, UK
Abstract :
External UHF couplers have been fitted to a 1000 MVA autotransformer as part of a project aimed at developing new transformer monitoring techniques. The couplers will supply valuable raw data from a transformer operating under normal service conditions. UHF signals were recorded while the transformer was re-energized and returned to load. Initially, some large discharges appeared, but these were short-lived. Background signal levels were low, indicating no significant interference problems. A small intermittent discharge signal was recorded and its characteristics are described. The possibilities for UHF monitoring of transformers are discussed, together with some of the remaining challenges
Keywords :
UHF detectors; autotransformers; insulation testing; power transformer insulation; power transformer testing; 1000 MVA; UHF sensor; autotransformer; discharge; power transformer monitoring; Couplers; Dielectrics; Fault location; Geographic Information Systems; Monitoring; Oil insulation; Partial discharges; Power transformer insulation; Power transformers; Testing;
Conference_Titel :
Electrical Insulation, 2000. Conference Record of the 2000 IEEE International Symposium on
Conference_Location :
Anaheim, CA
Print_ISBN :
0-7803-5931-3
DOI :
10.1109/ELINSL.2000.845528