DocumentCode :
2046007
Title :
Impact of advancements on automated relay testing over checking earth fault characteristics
Author :
Paduraru, C.
Volume :
1
fYear :
2004
fDate :
5-8 April 2004
Firstpage :
236
Abstract :
It is known that microprocessor based relay testing has become a challenge nowadays mainly because of the increased complexity. Most of the modem numerical relays have provisions to detect phase-to-ground faults for any type of neutral compensation. This raises the standard for everybody in the relay industry to introduce improved settings management as well as reliable test plans. To create a manual test plan becomes increasingly difficult so the focus on developing fully automated test plans is no longer a luxury but a necessity. This paper describes some of the challenges in developing an automatic test plan for earth fault detection functions.
Keywords :
automatic testing; earthing; fault diagnosis; power distribution faults; power distribution protection; relay protection; automated relay testing; earth fault detection; microprocessor relay testing; phase-to-ground faults; relay settings management;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
ISSN :
0537-9989
Print_ISBN :
0-86341-385-4
Type :
conf
DOI :
10.1049/cp:20040107
Filename :
1364850
Link To Document :
بازگشت