DocumentCode :
2046366
Title :
Parameters governing the AC and LI flashover strength of interfaces between epoxy resin tubes and transformer oil
Author :
Krins, M. ; Borsi, H. ; Gockenbach, E.
Author_Institution :
Scherring-Inst. of High Voltage Tech. & Eng., Hannover Univ., Germany
fYear :
2000
fDate :
2000
Firstpage :
431
Lastpage :
434
Abstract :
This paper reports on experimental investigations dealing with the impact of the temperature, the oil humidity, and the carbon content on the breakdown strength of oil gaps and the flashover behavior of glass-fiber reinforced epoxy resin tubes embedded in transformer oil. The measurements were carried out in a nearly uniform electrical field with an electrode arrangement being similar to the electrode/insulation configuration that is applied in on-load tap changers of power transformers. The contribution reveals that besides the breakdown values of the oil gap also the flashover behavior of the tubes is to a high extent determined by the relative oil humidity. Moreover it will be shown that in carbonized oil the flashover strength of the tubes needs not necessarily to be lower than in clean oil
Keywords :
electric breakdown; epoxy insulation; flashover; glass fibre reinforced plastics; power transformer insulation; transformer oil; AC flashover strength; LI flashover strength; carbon content; glass fiber reinforced epoxy resin tube; interfacial breakdown strength; oil gap; oil humidity; on-load tap changer; power transformer; temperature dependence; transformer oil; Electric breakdown; Electric variables measurement; Electrodes; Epoxy resins; Flashover; Humidity; Oil insulation; Petroleum; Power measurement; Temperature;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2000. Conference Record of the 2000 IEEE International Symposium on
Conference_Location :
Anaheim, CA
ISSN :
1089-084X
Print_ISBN :
0-7803-5931-3
Type :
conf
DOI :
10.1109/ELINSL.2000.845541