• DocumentCode
    2047543
  • Title

    Strategies for fault conditions that challenge distance protection

  • Author

    Bishop, P.R. ; Richards, S.

  • Volume
    2
  • fYear
    2004
  • fDate
    5-8 April 2004
  • Firstpage
    461
  • Abstract
    Based on practical experience, this paper summarises how selected power system fault conditions can affect distance protection and strategies for the protection to deal with these challenges. Fault conditions discussed in this paper are double phase to ground faults where quadrilateral zone overreach can occur, faults with high frequency components that can affect memory polarisation and single phase faults in single pole tripping applications where three phase trip conversion may occur.
  • Keywords
    power transmission faults; power transmission protection; relay protection; distance protection; double phase-ground faults; fault condition strategies; high frequency component faults; memory polarisation; power transmission faults; power transmission protection; quadrilateral zone overreach; relay protection; single phase faults; single pole tripping applications; three phase trip conversion;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2004. Eighth IEE International Conference on
  • ISSN
    0537-9989
  • Print_ISBN
    0-86341-385-4
  • Type

    conf

  • DOI
    10.1049/cp:20040161
  • Filename
    1364915