DocumentCode :
2047710
Title :
Insufficiency of watt-metric protection in resonant grounded networks
Author :
Kulis, I.G. ; Marusic, Ante ; Zutobradic, S.
Author_Institution :
Energy Inst. "Hrvoje Pozar", Zagreb, Croatia
Volume :
2
fYear :
2004
fDate :
5-8 April 2004
Firstpage :
486
Abstract :
Implementation of resonant grounding in the medium voltage (MV) rural distribution networks is in the process of consideration in Croatia. For analytical purposes, some calculations on a proposed ´typical´ rural distribution network are conducted followed by the presentation of live measurements on a similar real network. Based on calculations, influence of resonant grounding on watt-metric protection behaviour is presented in this article. This influence is compared with data found in the literature and those obtained by measurements.
Keywords :
earthing; fault diagnosis; power distribution faults; power distribution protection; Croatia; earth-fault protection; power distribution faults; power distribution protection; resonant grounded networks; rural distribution networks; watt-metric protection;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
ISSN :
0537-9989
Print_ISBN :
0-86341-385-4
Type :
conf
DOI :
10.1049/cp:20040167
Filename :
1364921
Link To Document :
بازگشت