Title :
Effect of CVTs on power system monitoring and fault recording
Author :
Ghassemi, F. ; Merron, J. ; Cole, D. ; Gale, P.
Author_Institution :
Qualitrol Hathaway Instruments, UK
Abstract :
A new technique for high frequency, high-speed transient measurements using capacitor voltage transformers (CVT) in high voltage systems is examined by simulation and field tests. It was shown that the new technique, which is based on the measurement of currents in CVTs can be used to monitor fast transients without any need for special high voltage instrument transformers or wide bandwidth voltage dividers. This was confirmed by field tests where a very close correlation was achieved between the measurements by the new technique and those obtained through resistive voltage divider.
Keywords :
electric current measurement; fault diagnosis; power system faults; power system measurement; power system protection; power system transients; power transformers; recorders; capacitor voltage transformers; current measurement; fault recording; power system faults; power system monitoring; power system protection; power system transient measurement;
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
Print_ISBN :
0-86341-385-4
DOI :
10.1049/cp:20040174