Title :
Evolution of numerical generator protection for application to a Powerformer
Author :
Lloyd, G.J. ; Yip, T.H. ; Lin, X. ; Lindahl, G.
Author_Institution :
AREVA T&D Ltd - Energy Autom. & Inf., UK
Abstract :
This paper discusses a protection relay under development which provides all the fundamental functionality required for the protection and monitoring of generating plant. In addition, it provides advanced protection necessary for the Powerformer, including:compensated generator differential protection which compensates for the standing capacitive charging current resulting from the stator winding cables, phase selective 100% stator earth fault protection, suitable for a high impedance earthed or a solidly earthed network, without the need for voltage measurement at the neutral. breaker failure protection with single pole stuck detection and overvoltage protection for parallel machines connected directly to the busbar.
Keywords :
earthing; machine protection; overvoltage protection; power generation faults; power generation protection; relay protection; synchronous generators; Powerformer; breaker failure protection; differential protection; numerical generator protection; overvoltage protection; phase selective stator earth fault protection; power generation faults; power generation protection; synchronous machine;
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
Print_ISBN :
0-86341-385-4
DOI :
10.1049/cp:20040184