DocumentCode :
2048292
Title :
A new islanding detection algorithm for distributed generations interconnected with utility networks
Author :
Jang, S.I. ; Kim, K.H.
Author_Institution :
Seoul Nat. Univ., South Korea
Volume :
2
fYear :
2004
fDate :
5-8 April 2004
Firstpage :
571
Abstract :
This paper introduced and proposed the voltage unbalance of distributed generation (DG) terminal output as new monitoring parameter for power islanding detection. This paper also presented a simple and novel detection algorithm, which effectively combines the detection results of the conventional parameter, voltage magnitude, and a newly proposed parameter. We tested the proposed method using several distribution network conditions including not only islanding operation conditions, but also non-islanding conditions of normal network load variations. The test results showed that the proposed parameters and algorithm are capable of correctly detecting the islanding operation not affected by variation of DG loading and also have a good selectivity for islanding conditions and non-islanding conditions.
Keywords :
distributed power generation; power generation faults; power generation protection; voltage measurement; distributed power generation; islanding detection algorithm; power generation faults; power generation protection; voltage magnitude detection; voltage unbalance;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
ISSN :
0537-9989
Print_ISBN :
0-86341-385-4
Type :
conf
DOI :
10.1049/cp:20040188
Filename :
1364942
Link To Document :
بازگشت