Title :
Fault transient calculation on condition of system swing and analysis of relaying protection
Author :
Wang, Q.P. ; Dong, X.Z. ; Zhou, S.X. ; Chen, C.Y.
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Abstract :
For calculating the fault transient on condition of system swing, changes of frequency and angle are taken into account in this paper. Considering the salient-pole reaction, stator coil transient and rotor coil mechanical characteristics, the united synthetic companion model of synchronous generators is built by integrating the electromagnetic transient, mechanical transient and port equation of synchronous generators. Based on the spectral analysis, the modified Euler model can not only avoid oscillation of numerical calculation but also improve the simulating accuracy. The fault electromagnetic transient on condition of system swing is simulated by synthetic companion model of generator. Distance protection element of LFP-901A, the transmission line protection, is taken for example to analyze action of the protection and its swing block component on condition of system swing.
Keywords :
coils; power system faults; power system protection; power system transients; relay protection; rotors; stators; synchronous generators; LFP-901A; distance protection; electromagnetic transient faults; electromagnetic transient integration; fault transient calculation; frequency changes; mechanical transient integration; modified Euler model; phase angle changes; power system swings; relay protection; rotor coil mechanical characteristics; salient-pole reaction; stator coil transient; synchronous generator port equation integration;
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
Print_ISBN :
0-86341-385-4
DOI :
10.1049/cp:20040202