• DocumentCode
    2049226
  • Title

    Distributed bus differential relay becomes the complete integrated protection system for the substation

  • Author

    Amantegui, J. ; Quintanilla, R.

  • Author_Institution
    IBERDROLA, Spain
  • Volume
    2
  • fYear
    2004
  • fDate
    5-8 April 2004
  • Firstpage
    734
  • Abstract
    Integrated protection and control bay IEDs can become bus differential bay IEDs, that includes a breaker failure protection also, with a moderate increase in cost. So, it is possible to think in applying these functions down to 30 kV; where, traditionally, they are not been applied. The consequence is to improve quality and to increase safety for people and to minimize damages to high voltage equipment. On the other hand, distributed bus differential architecture offers the base to merge every protection and control functions needed in a substation, including communications. The convergence of both facts, enable the creation of a complete protection and control system. A system offering flexibility to the user and the application to determine the level of integration depending to the reliability, safety, and physical redundancy requirements.
  • Keywords
    power system control; power system faults; power system protection; relay protection; substation automation; substation protection; breaker failure protection; bus differential bay IED; distributed bus differential relay; integrated substation protection system; intelligent electronic device; substation control;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2004. Eighth IEE International Conference on
  • ISSN
    0537-9989
  • Print_ISBN
    0-86341-385-4
  • Type

    conf

  • DOI
    10.1049/cp:20040227
  • Filename
    1364981