Title :
Synchronized phasor measurement in protective relays for protection, control, and analysis of electric power systems
Author :
Benmouyal, G. ; Schweitzer, E.O. ; Guzman, A.
Author_Institution :
Schweitzer Eng. Labs. Inc., USA
Abstract :
The advent of satellite-based time-keeping systems and advances in computer technology have made possible protective relay sampling synchronization within 1 μs. These relays can now provide synchronized phasor measurements that eliminate the need to have different devices for protection, control, and electric power system analysis for system-wide applications and traditional protection applications. System-wide applications have different sampling and signal processing requirements than do traditional protection applications. This paper proposes combining the aforementioned applications in a single device with a flexible signal processing system.
Keywords :
phase measurement; power system control; power system faults; power system protection; relay protection; synchronisation; flexible signal processing system; power system control; power system protection; protective relays; satellite-based time-keeping; synchronized phasor measurement; system-wide applications;
Conference_Titel :
Developments in Power System Protection, 2004. Eighth IEE International Conference on
Print_ISBN :
0-86341-385-4
DOI :
10.1049/cp:20040246