• DocumentCode
    2049688
  • Title

    Synchronized phasor measurement in protective relays for protection, control, and analysis of electric power systems

  • Author

    Benmouyal, G. ; Schweitzer, E.O. ; Guzman, A.

  • Author_Institution
    Schweitzer Eng. Labs. Inc., USA
  • Volume
    2
  • fYear
    2004
  • fDate
    5-8 April 2004
  • Firstpage
    814
  • Abstract
    The advent of satellite-based time-keeping systems and advances in computer technology have made possible protective relay sampling synchronization within 1 μs. These relays can now provide synchronized phasor measurements that eliminate the need to have different devices for protection, control, and electric power system analysis for system-wide applications and traditional protection applications. System-wide applications have different sampling and signal processing requirements than do traditional protection applications. This paper proposes combining the aforementioned applications in a single device with a flexible signal processing system.
  • Keywords
    phase measurement; power system control; power system faults; power system protection; relay protection; synchronisation; flexible signal processing system; power system control; power system protection; protective relays; satellite-based time-keeping; synchronized phasor measurement; system-wide applications;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2004. Eighth IEE International Conference on
  • ISSN
    0537-9989
  • Print_ISBN
    0-86341-385-4
  • Type

    conf

  • DOI
    10.1049/cp:20040246
  • Filename
    1365000