DocumentCode :
2056029
Title :
An investigation into the operation life of transformers
Author :
Xin Wang ; Xin Zhang
Author_Institution :
Gansu Electr. Power Res. Inst., Lanzhou, China
fYear :
2012
fDate :
10-14 Sept. 2012
Firstpage :
1
Lastpage :
4
Abstract :
This paper presents results of a study on solid insulation aging of a number of oil-immersed power transformers, some of them have operated for more than 40 years. The contents of furfurol were measured, in addition to that of dissolved gases in transformer oil, by applying the HPLC method. Based on measured data and the traditional theory of solid insulation aging, it is suggested that the aging of solid insulation in these transformers is not serious even after 50 years´ of continued operation, because there has been no local overheating or sustained transformer overload during their operation.
Keywords :
ageing; power transformer insulation; transformer oil; HPLC method; oil-immersed power transformers; solid insulation aging theory; sustained transformer overload; transformer operation life; Content of furfurol; insulation aging; solid insulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electricity Distribution (CICED), 2012 China International Conference on
Conference_Location :
Shanghai
ISSN :
2161-7481
Print_ISBN :
978-1-4673-6065-4
Electronic_ISBN :
2161-7481
Type :
conf
DOI :
10.1109/CICED.2012.6508406
Filename :
6508406
Link To Document :