DocumentCode
2056268
Title
Simplified modelling of wind farms for voltage dip transients
Author
Ben Kilani, Khadija ; Elleuch, Mohamed
Author_Institution
ENIT-L.S.E., Univ. of Tunis El Manar, Tunis le Belvédère, Tunisia
fYear
2012
fDate
20-23 March 2012
Firstpage
1
Lastpage
6
Abstract
This paper addresses the issue of simplified modelling of large scale wind farms and its impact on the accuracy of dynamic systems responses to grid transient faults. We propose a simplified model consisting of a detailed wind turbine model with scaled-up outputs, versus the conventional aggregate representation of wind farms. The simplification methods are compared for their suitability to grid voltage dip transients of increased duration. The methods are applied to a wind farm split into three coherent clusters. The results show that the aggregate machine model is suitable for static and short transient grid faults, but limited in voltage ride through studies of grid faults of longer clearing time.
Keywords
power generation faults; transient analysis; wind power plants; wind turbines; aggregate machine model; detailed wind turbine model; large-scale wind farms; short-transient grid fault; static grid fault; voltage dip transients; wind farm simplified modelling; Aggregates; Generators; Reactive power; Rotors; Voltage fluctuations; Wind farms; Wind turbines; Wind farm simplified modelling; model aggregation; transient stability studies;
fLanguage
English
Publisher
ieee
Conference_Titel
Systems, Signals and Devices (SSD), 2012 9th International Multi-Conference on
Conference_Location
Chemnitz
Print_ISBN
978-1-4673-1590-6
Electronic_ISBN
978-1-4673-1589-0
Type
conf
DOI
10.1109/SSD.2012.6198082
Filename
6198082
Link To Document