• DocumentCode
    2057737
  • Title

    New corona ultraviolet detection system and fault location method

  • Author

    Bo Hu ; Li-Xin Ma ; Shu-Juan Yuan ; Bai Yang

  • Author_Institution
    Sch. of Opt.-Electr. & Comput. Eng., Univ. of Shanghai for Sci. & Technol., Shanghai, China
  • fYear
    2012
  • fDate
    10-14 Sept. 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Corona discharge often occurs in high voltage equipment and transmission lines with the elevating of the electrical network capacity and voltage level, which can lead to noise, loss of power and interference with TV and radio. Worse, the insulation of power equipment might be badly destroyed. Therefore, corona discharges in power system get more attention. In this paper, a non-line monitoring system of double channel ultraviolet is introduced for detecting the UV spectrum in ultraviolet sun-blind band (240~280 nm) of the corona discharge in the high voltage equipment. And also, the IHS space image fusion algorithm is proposed to locate where corona discharge occurs.
  • Keywords
    corona; fault location; image fusion; power engineering computing; ultraviolet spectra; IHS space image fusion algorithm; TV; UV spectrum; corona discharge; corona ultraviolet detection system; electrical network capacity; fault location method; high voltage equipment; interference; power equipment; radio; transmission lines; ultraviolet sun-blind band; voltage equipment; voltage level; Corona discharge; Double channel; Image fusion; Sun-blind ultraviolet detection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2012 China International Conference on
  • Conference_Location
    Shanghai
  • ISSN
    2161-7481
  • Print_ISBN
    978-1-4673-6065-4
  • Electronic_ISBN
    2161-7481
  • Type

    conf

  • DOI
    10.1109/CICED.2012.6508475
  • Filename
    6508475