DocumentCode :
2058222
Title :
Influence of Switching Frequency on Eddy-Current Losses in a Three-Phase, Three-Limb Transformer Core Subjected to PWM Voltage Excitation
Author :
Yao, Xiao Guang ; Moses, Anthony J. ; Sagarduy, Juan ; Anayi, Fatih J.
Author_Institution :
Wolfson Centre for Magnetics, School of Engineering-Cardiff University, Queen´´s Building-The Parade, Cardiff-CF24 3AA, Wales, United Kingdom. E-Mail: YaoXG@Cardiff.ac.uk
fYear :
2007
fDate :
12-14 April 2007
Firstpage :
324
Lastpage :
329
Abstract :
Transformers are key elements in power generation, transmission and distribution systems. Transformers under PWM supply are essential elements in industrial applications such as active power line conditioning, electrified railway power systems, PWM DC-DC power converters. Assessing the performance of transformers under PWM supplies is relevant to these applications. In this paper, the variation of iron losses with switching frequency in the range of 1 kHz - 3 kHz in a three-phase, three-limb transformer core under no-load conditions was measured. Classical eddy-current losses were calculated for various values of modulation index and magnetization conditions (frequency 50 Hz, 100 Hz; induction 1.3 T, 1.5 T). Results showed a reduction of the eddy-current component of loss by up to 40% at low frequency of magnetization and low modulation index with high switching frequency.
Keywords :
Electrical equipment industry; Electricity supply industry; Magnetization; Power generation; Pulse width modulation; Pulse width modulation converters; Rail transportation; Railway electrification; Switching frequency; Transformer cores;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering, Energy and Electrical Drives, 2007. POWERENG 2007. International Conference on
Conference_Location :
Setubal, Portugal
Print_ISBN :
978-1-4244-0895-5
Electronic_ISBN :
978-1-4244-0895-5
Type :
conf
DOI :
10.1109/POWERENG.2007.4380213
Filename :
4380213
Link To Document :
بازگشت