DocumentCode
2059140
Title
The project of distributed generation connection based on graded-controlling output power of generators
Author
Junjun Zhang ; Xiaoyu Wei ; Jiali Zhuang
Author_Institution
Songjiang Power Supply Co., SMEPC, Shanghai, China
fYear
2012
fDate
10-14 Sept. 2012
Firstpage
1
Lastpage
4
Abstract
The paper describes the particularity of the mode of the distributed generation access to the power system but not allowed to transmit power to the system. A project is proposed that monitoring the load on user side in real time, and recording the load´s supply and demand, then dividing the generator´s power by the ratio of the generator and the user´s total load for several degrees. Once the load and generator output reach the critical balance, a part of the generators will be cut according to the degree, which can not only avoid the adverse-power protection acting, but also make a full use of the distributed generation to promote its economic efficiency.
Keywords
distributed power generation; power system measurement; adverse-power protection; distributed generation access; graded-controlling output power; load monitoring; power system;