• DocumentCode
    2060293
  • Title

    On-line monitoring of winding deformation of power transformer

  • Author

    Xu, D.K. ; Huang, J.H. ; Li, Y.M.

  • Author_Institution
    R&I Center, GuoDian NanJing Autom. Co. Ltd., China
  • fYear
    2001
  • fDate
    2001
  • Firstpage
    853
  • Lastpage
    856
  • Abstract
    The feasibility of estimating transformer winding deformation by measuring short-circuit reactance is expounded. Based on the theoretical research, the on-line measurement system for short-circuit reactance of a transformer is proposed. The study on a power transformer in actual operating condition shows that the on-line method is satisfactory for detecting short-circuit reactance variations with high degree of accuracy and good stability, and can be used for detecting deformation in the transformer windings
  • Keywords
    computerised monitoring; electric reactance measurement; fault diagnosis; power transformers; short-circuit currents; transformer windings; 10 kV; 110 kV; 31500 kVA; on-line method; on-line monitoring; operating condition; power transformer; short-circuit reactance measurement; stability; transformer winding deformation estimation; winding deformation; Accidents; Equivalent circuits; Impedance; Monitoring; Oil insulation; Power system stability; Power transformer insulation; Power transformers; Testing; Windings;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 2001. (ISEIM 2001). Proceedings of 2001 International Symposium on
  • Conference_Location
    Himeji
  • Print_ISBN
    4-88686-053-2
  • Type

    conf

  • DOI
    10.1109/ISEIM.2001.973812
  • Filename
    973812