• DocumentCode
    2060762
  • Title

    Research on transformer syspathetic inrush current in initail period of power system

  • Author

    Wei Gong ; Junyong Liu ; Xingqi He

  • Author_Institution
    Sch. of Electr. Eng. & Inf., Sichuan Univ., Chengdu, China
  • fYear
    2012
  • fDate
    10-14 Sept. 2012
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    In the initial period of power system restoration, charging the transformer without load will result in sympathetic inrush current appearing in its adjacent transformer. The sympathetic inrush current will appear as a result of the saturation.. In view of fundamental representations of flux linkage, with the help of the integral model of sympathetic inrush of two shunt-wound transforms, the paper derives a formula that the sympathetic inrush current value is decided by the integral value of public bus voltage in a period. From the formula, this paper get the generation reason of sympathetic inrush current that public bus voltage in two shunt-wound transforms depresses suddenly so that linkage of neighboring running transformer changes. Then analyzes the influence of system resistance on sympathetic inrush current. This analysis provides a sound theoretical basis for a complete understanding of the phenomenon.
  • Keywords
    power system restoration; power transformers; flux linkage; initial period; integral model; power system restoration; public bus voltage; shunt-wound transforms; transformer sympathetic inrush current; initial period of restoration; sympathetic inrush current; system resistance; transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2012 China International Conference on
  • Conference_Location
    Shanghai
  • ISSN
    2161-7481
  • Print_ISBN
    978-1-4673-6065-4
  • Electronic_ISBN
    2161-7481
  • Type

    conf

  • DOI
    10.1109/CICED.2012.6508595
  • Filename
    6508595