• DocumentCode
    2063066
  • Title

    Discrimination method of power frequency ferroresonance in GIS

  • Author

    Shuang Li ; Honggang Han ; Wei Zhang

  • Author_Institution
    Liaoning Electr. Power Res. Inst., China
  • fYear
    2012
  • fDate
    10-14 Sept. 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Ferroresonance over-voltage is one of the most important factors to impact the inner insulation of electrical appliances. The damage to appliance caused by ferroresonance over-voltage accounted for a great majority proportion in power system. A criterion in neutral-ungrounded power system was deducted in detail to estimate whether the ferroresonance will occur in power system from one manner of working transiting to another manner of working. This criterion deducted by means of analytical method expresses the relationship between circuit equivalent resistance and critical resistance, which can be used to decide the zero-sequence resistance value added to the secondary coil of potential transformer to eliminate the ferroresonance over-voltage. The availability of this criterion was verified under two working states via a practical gas insulated substation.
  • Keywords
    coils; electric resistance; ferroresonance; gas insulated substations; overvoltage protection; potential transformers; underground transmission systems; GIS; circuit equivalent resistance; critical resistance; electrical appliances insulation; ferroresonance overvoltage; gas insulated substation; neutral ungrounded power system; potential transformer; power frequency ferroresonance; secondary coil; zero sequence resistance value;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2012 China International Conference on
  • Conference_Location
    Shanghai
  • ISSN
    2161-7481
  • Print_ISBN
    978-1-4673-6065-4
  • Electronic_ISBN
    2161-7481
  • Type

    conf

  • DOI
    10.1109/CICED.2012.6508683
  • Filename
    6508683