• DocumentCode
    2064105
  • Title

    Electromagnetic interference due to HVDC transmission line faults

  • Author

    Yixin Yang ; Jinxi Ma ; Fortin, Simon ; Dawalibi, Farid

  • Author_Institution
    Safe Eng. Services & Technol. Ltd., Canada
  • fYear
    2012
  • fDate
    10-14 Sept. 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper presents a study of electromagnetic interference to pipelines due tonearby 500 kV HVDC transmission line faults.While there is a large volume of publications addressing the issues of alternating EMI issues, the authors are not aware of publicly available publications addressing the issues of inductive interference from HVDC lines under fault conditions. The objective of this paper is to fill in this gap.The study focuses on magnetic (inductive) interference to the pipelines caused by the transient nature of the fault current. Modelling techniques for this type of studies are described and computation results for the induced potential on a pipeline during a fault are presented.
  • Keywords
    HVDC power transmission; electromagnetic interference; fault currents; interference suppression; pipelines; power transmission faults; power transmission lines; EMI; HVDC transmission line fault; electromagnetic interference; fault condition; inductive interference; inductive objective; magnetic interference; pipelines; transient fault current; voltage 500 kV;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2012 China International Conference on
  • Conference_Location
    Shanghai
  • ISSN
    2161-7481
  • Print_ISBN
    978-1-4673-6065-4
  • Electronic_ISBN
    2161-7481
  • Type

    conf

  • DOI
    10.1109/CICED.2012.6508724
  • Filename