Title :
A study of phase-wire voltage increase due to corona wave-deformation
Author :
Ametani, A. ; Fukuda, N. ; Sekioka, S. ; Higuchi, T. ; Kato, Y.
Author_Institution :
Doshisha Univ., Kyoto, Japan
Abstract :
The paper presents measured results of the corona wave-deformation on a test line with various boundary conditions corresponding to a substation. The measured results have shown an increase of the phase-wire voltage at the receiving end under a certain boundary condition, while the ground-wire voltage is always decreased by the corona wave-deformation. The phenomenon is theoretically investigated, and it has been made clear that the increase is, in principle, caused by heavier attenuation of a traveling-wave on a ground wire than that on a phase wire, and the negative reflection of the traveling-wave from the ground wire to the phase wire. The condition of the voltage increase has been theoretically derived
Keywords :
corona; power overhead lines; power system measurement; substations; voltage measurement; boundary conditions; certain boundary condition; corona wave-deformation; ground wire; negative reflection; phase-wire voltage increase; receiving end; substation; traveling-wave attenuation; voltage increase; Attenuation; Boundary conditions; Corona; Phase measurement; Power transmission lines; Substations; Testing; Transmission line measurements; Voltage; Wire;