• DocumentCode
    2072365
  • Title

    Determination of optimal shielding angles in shielded transmission line design

  • Author

    Holt, R. ; Nguyen, T.T.

  • Author_Institution
    Energy Syst. Centre, Western Australia Univ., Nedlands, WA, Australia
  • Volume
    4
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    2892
  • Abstract
    The paper develops a general formulation that gives expressions for the exposure distance of transmission line conductors to direct lightning strikes in terms of striking distances, conductor heights, cross-arm lengths and shielding angles. The expressions are applicable to different electrogeometric models (EGM). They provide the basis on which optimal shielding angle is determined in the design of earthwires. Constrained minimisation of the exposure distance gives the optimal value for shielding angle. The expressions are validated using the published field results. Using the general expressions developed, investigations are carried out to identify the factors on which optimal shielding angle depends and to quantify the degree of dependencies. Sensitivity of the optimal shielding angle to different EGMs is evaluated in the paper
  • Keywords
    lightning; overhead line conductors; power overhead lines; shielding; conductor heights; constrained minimisation; cross-arm lengths; direct lightning strikes; earthwires determination; electrogeometric models; optimal shielding angle; optimal shielding angles determination; sensitivity; shielded transmission line design; shielding angles; striking distances; transmission line conductors exposure distance; Australia; Closed-form solution; Conductors; Earth; Equations; Genetic expression; Lightning; Transmission lines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Winter Meeting, 2000. IEEE
  • Print_ISBN
    0-7803-5935-6
  • Type

    conf

  • DOI
    10.1109/PESW.2000.847335
  • Filename
    847335