DocumentCode
2072948
Title
Corona characteristics of conductors due to oscillatory lightning surges
Author
Jia, Wang ; Xiaoqing, Zhang
Author_Institution
Sch. of Electron. Inf., Beijing Univ. of Civil Eng. & Archit., Beijing
fYear
2008
fDate
19-23 May 2008
Firstpage
690
Lastpage
693
Abstract
Existing calculations of lightning overvoltage are based on double exponential impulses. In fact, damped oscillatory impulses are closer to the actual status than double exponential impulses. An experimental study of corona characteristics under unipolar oscillation impulses is described in this paper which exposed the change rule of q-u curves by changing parameter of waveshape. It also explains the origin of error in lightning overvoltage calculation based on q-u characteristics of double exponential impulses.
Keywords
corona; lightning; lightning protection; overvoltage; surge protection; surges; conductors; corona; double exponential impulses; oscillatory lightning surges; unipolar oscillation impulses; Conductors; Corona; Current measurement; Electrodes; Electromagnetic compatibility; Frequency; Lightning; Resistors; Surge protection; Voltage control; damped oscillatory impulses; lightning overvoltage calculation; q-u curves;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility and 19th International Zurich Symposium on Electromagnetic Compatibility, 2008. APEMC 2008. Asia-Pacific Symposium on
Conference_Location
Singapore
Print_ISBN
978-981-08-0629-3
Electronic_ISBN
978-981-08-0629-3
Type
conf
DOI
10.1109/APEMC.2008.4559969