DocumentCode
2074093
Title
Calculation of the transient electric field generated by complicated conductor structure in substation
Author
Chen, Jiahong ; Zhang, Mingxia ; Cui, Xiang ; Zhao, Zhibin
Author_Institution
Wuhan high voltage Res. Inst. of SGCC, Wuhan
fYear
2008
fDate
19-23 May 2008
Firstpage
895
Lastpage
898
Abstract
Based on the continuity of potential on conductor surface, the transient electromagnetic field resulting from line fault is calculated by using MoM. With the complex resistivity introduced, the effect of grounding grid was also included. The proposed approach, which is validated by comparison with other method, can be used to analyse the wave process and space electromagnetic fields of arbitrary constituted conductor structure under the cases of lightning strike and line fault with frequency lower than several hundreds kHz. Both the power frequency electromagnetic field and the transient electric field of a practical substation under fault were evaluated as an application.
Keywords
conductors (electric); electromagnetic fields; method of moments; power overhead lines; MoM; complex resistivity; complicated conductor structure; space electromagnetic fields; transient electric field; Conductivity; Conductors; Electromagnetic analysis; Electromagnetic fields; Electromagnetic transients; Frequency; Power system transients; Substations; Switches; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility and 19th International Zurich Symposium on Electromagnetic Compatibility, 2008. APEMC 2008. Asia-Pacific Symposium on
Conference_Location
Singapore
Print_ISBN
978-981-08-0629-3
Electronic_ISBN
978-981-08-0629-3
Type
conf
DOI
10.1109/APEMC.2008.4560020
Filename
4560020