• DocumentCode
    2079255
  • Title

    Analysis of stator ground protection schemes for hydro-generator of Three-Gorges power plant based on zero sequence voltages

  • Author

    Tai, Nengling ; Yin, Xianggen ; Chen, Deshu

  • Author_Institution
    Dept. of Electr. Eng., Huazhong Univ. of Sci. & Technol., Wuhan, China
  • Volume
    3
  • fYear
    2000
  • fDate
    23-27 Jan 2000
  • Firstpage
    1888
  • Abstract
    New mathematical models for the zero-sequence voltage of large hydro-generator on turn basis are used to study hydro-generator stator ground fault protection schemes in this paper. The evaluation and the comparison of the characteristics of some stator ground protection schemes are described by means of protection coverage-critical resistance curves. And the simulation results showed that those schemes would suffer low sensitivity when they are used to huge hydro-generators in Three-Gorges power plant. To overcome this disadvantage, new ground fault protection schemes with higher sensitivity based on fault components are developed in this paper
  • Keywords
    earthing; electrical faults; hydroelectric generators; hydroelectric power stations; machine protection; machine theory; stators; Three-Gorges hydropower plant; fault components; ground fault protection schemes; hydroelectric generator; mathematical models; protection coverage-critical resistance curves; sensitivity; simulation results; stator ground protection schemes; zero sequence voltages; Capacitance; Costs; Fault detection; Mathematical model; Power generation; Protection; Senior members; Stator windings; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Winter Meeting, 2000. IEEE
  • Print_ISBN
    0-7803-5935-6
  • Type

    conf

  • DOI
    10.1109/PESW.2000.847641
  • Filename
    847641