Decreasing momentary outages with specific distribution feeder improvements
Author :
Coate, Brian D. ; Wareham, Don C.
Author_Institution :
Tipmont REMC, Linden, IN, USA
Abstract :
This paper presents a cost-effective method of reducing momentary interruptions. Two main concepts are discussed. The first is targeting selected zones with increased maintenance to improve overall reliability of the entire feeder, and the second is overcurrent coordination for trip saving on the substation feeder circuit breaker. Trip saving is the intentional coordination of tap fuses off main feeders so that a fault on the tap will not cause a fast operation of the main breaker. Other topics discussed are the re-setting of instantaneous tripping of the substation breaker, use of tap reclosers, and increasing lightning/animal protection on key parts of the feeder
Keywords :
circuit breakers; lightning protection; maintenance engineering; overcurrent protection; power distribution faults; power distribution protection; power distribution reliability; substations; animal protection; cost-effective method; distribution feeder improvements; feeder reliability; lightning protection; maintenance improvements; momentary outages reduction; overcurrent coordination; substation feeder circuit breaker; tap fuses coordination; tap reclosers; trip saving; Animals; Circuit faults; Engineering management; Fuses; Lightning; Maintenance; Power system protection; Power system transients; Reliability engineering; Substation protection;