• DocumentCode
    2084197
  • Title

    A computational study of localised loss in a distribution transformer

  • Author

    Basak, A. ; Lloyd, G. ; Yu, C.H.

  • Author_Institution
    Wolfson Centre for Magnetics Technol., Univ. of Wales Coll. of Cardiff, UK
  • fYear
    1994
  • fDate
    12-14 Apr 1994
  • Firstpage
    56
  • Lastpage
    59
  • Abstract
    The localised loss in a 1000 kVA distribution transformer core model has been computed with the aid of a 386 microprocessor based personal computer using novel software. Overall core loss in the transformer model has been computed to be 1371 W at core flux density of 1.6 T. The loss measured in a commercial transformer core of similar geometry and rating was 1299 W thus giving a discrepancy of 5.6%
  • Keywords
    eddy current losses; finite element analysis; power system analysis computing; power transformers; transformer cores; 1.6 T; 1000 kVA distribution transformer core model; 1299 W; 1371 W; commercial transformer core; core flux density; core loss; distribution transformer; localised loss; software;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Computation in Electromagnetics, 1994. Second International Conference on
  • Conference_Location
    London
  • Print_ISBN
    0-85296-609-1
  • Type

    conf

  • DOI
    10.1049/cp:19940015
  • Filename
    324085