• DocumentCode
    2091004
  • Title

    Investigation of the Imbalance Current Compensation for Transformers Used in Electric Railways

  • Author

    Dai, Chenxi ; Sun, Yuanyuan

  • Author_Institution
    Coll. of Electr. Eng., Zhejiang Univ., Hangzhou, China
  • fYear
    2010
  • fDate
    28-31 March 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Different transformer connections have different influences on the imbalance current introduced by the electric traction load. From transformers´ symmetrical components matrices, the conditions under which there will be lest current injected into the primary windings of the transformer are studied. Capacitors or inductors can be installed to compensate the traction load to reach these conditions. Based on the deduced balance criteria, the compensation capacities for several specially connected transformers are researched. Analysis found out that for Scott transformer, Le-Blanc transformer and Modified Wood-bridge transformer, it is useful to install combination of inductors and capacitors on the secondary winding of transformers in order to reduce imbalance current.
  • Keywords
    current transformers; electric current; power supply quality; railway electrification; Le-Blanc transformer; Modified Wood-bridge transformer; Scott transformer; capacitors; deduced balance criteria; electric railways; electric traction load; imbalance current compensation; inductors; primary windings; secondary winding; Capacitors; Impedance; Inductors; Phase transformers; Power supplies; Rail transportation; Substations; Symmetric matrices; Traction motors; Virtual colonoscopy;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-4812-8
  • Electronic_ISBN
    978-1-4244-4813-5
  • Type

    conf

  • DOI
    10.1109/APPEEC.2010.5448337
  • Filename