DocumentCode
2094833
Title
Very fast electromagnetic transients in air insulated substations and gas insulated substations due to disconnector switching
Author
Carsimamovic, Salih ; Bajramovic, Zijad ; Ljevak, Miroslav ; Veledar, Meludin
Author_Institution
Fac. of Electr. Eng., Sarajevo Univ., Bosnia-Herzegovina
Volume
2
fYear
2005
fDate
8-12 Aug. 2005
Firstpage
382
Abstract
Very fast electromagnetic transients (VFT) in air insulated substations (AIS) and gas insulated substations (GIS) caused by switching operation of disconnectors are investigated. Results obtained from very extensive field tests and from digital simulations as well as a comparison between field tests and calculation results of VFT in AIS and GIS due to disconnector switching are presented. Field tests of disconnector switching in 220 kV air insulated substations Grabovica and Kakanj as well as test circuit of 110 kV GIS section are performed. Digital simulation of VFT for different models of power network are performed using EMTP-ATP.
Keywords
air insulation; electromagnetic compatibility; gas insulated substations; switching; testing; 110 kV; 220 kV; Grabovica; Kakanj; air insulated substations; disconnector switching; gas insulated substations; very fast electromagnetic transients; Circuit testing; Contacts; Frequency; Gas insulation; Geographic Information Systems; Substations; Surges; Switchgear; Switching circuits; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility, 2005. EMC 2005. 2005 International Symposium on
Print_ISBN
0-7803-9380-5
Type
conf
DOI
10.1109/ISEMC.2005.1513544
Filename
1513544