DocumentCode
2100646
Title
Computation of busbars local electromagnetic force densities connected to 3-pulse rectifier load over a complete cycle
Author
Abd-El-Aziz, Mona M. ; Nashed, Maged N F ; Adly, Amr A. ; Abou-El-Zahab, Essam-El-Din M.
Author_Institution
Electron. Res. Inst., Giza
fYear
2008
fDate
12-15 March 2008
Firstpage
550
Lastpage
554
Abstract
All power system substations use three phase parallel busbars in the power distribution between loads. These busbars are subjected to electromagnetic forces which may cause their permanent deformation, break of insulating supports and an excess vibrational stresses applied on the busbars. From the factors affect these forces is whether the busbars currents have harmonic content or not. This paper presents an analytical approach from which overall forces and local force densities can be calculation. Busbars currents contain harmonics are used in this approach implementation. These currents are taken from a simulated model of 3-pulse rectifier, which is compared with an experimental model to give well qualitative current values.
Keywords
busbars; electromagnetic forces; harmonic analysis; power distribution; power system harmonics; rectifier substations; switchgear insulation; 3pulse rectifier load; busbars currents harmonics; busbars local electromagnetic force densities; power distribution; power system substations; three phase parallel busbars; Circuit faults; Conducting materials; Electromagnetic forces; Insulation; Power system harmonics; Power system modeling; Rectifiers; Stress; Substations; Vibrations; 3 Phase parallel busbars; 3-pulse rectifier; Busbars currents contain harmonics; electromagnetic force;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Conference, 2008. MEPCON 2008. 12th International Middle-East
Conference_Location
Aswan
Print_ISBN
978-1-4244-1933-3
Electronic_ISBN
978-1-4244-1934-0
Type
conf
DOI
10.1109/MEPCON.2008.4562336
Filename
4562336
Link To Document