The Optimized Match Method Enhances the Energy Efficiency Ratio (EER) of Room Air-Conditioner
         
        
            Author : 
Wang Zhiyuan ; He Tao ; Xu Zhiliang ; Luohao ; Dang Hongchang
         
        
            Author_Institution : 
Coll. of Vehicle & Power, Henan Univ. of Sci. & Technol., Luoyang, China
         
        
        
        
        
        
            Abstract : 
In this paper, an experimental study was conducted on domestic air-conditioner refrigeration system to increase the system energy efficiency ratio (EER). First, different types of high efficiency compressors were tested and selected. Second, inner-grooved copper tubes which had fins with hydrophilic membrane, together with the indoor and outdoor helical fans were employed to improve the heat convection efficiency. Third, the relationship between capillary´s optimum length and refrigerant charge quantity was confirmed experimentally. By these means, the system EER can reach up to 3.2, which meets the demands of National standards of China.
         
        
            Keywords : 
air conditioning; compressors; domestic appliances; fans; refrigeration; capillary optimum length; domestic air-conditioner refrigeration system; energy efficiency ratio; high efficiency compressors; hydrophilic membrane; indoor helical fans; inner-grooved copper tubes; optimized match method; outdoor helical fans; refrigerant charge quantity; room air-conditioner; Biomembranes; Compressors; Cooling; Copper; Energy consumption; Energy efficiency; Optimization methods; Refrigerants; Refrigeration; Testing;
         
        
        
        