DocumentCode :
2106816
Title :
Backup considerations for line current differential protection
Author :
Hodder, Steven ; Kasztenny, Bogdan ; Fischer, Normann
fYear :
2012
fDate :
2-5 April 2012
Firstpage :
96
Lastpage :
107
Abstract :
Line current differential (87L) protection relies on communications for the exchange of current values and, if applied over asymmetrical channels, on external time sources for current alignment. Proper engineering of 87L schemes calls for a backup strategy that considers the loss of communications and/or the loss of external time sources. This paper reviews various channel and time backup strategies for 87L protection schemes and considers utility practices and regulatory constraints related to line protection redundancy, forced line outages, preferred balance between protection dependability and security, ability to provide adequate protection coverage with distance or overcurrent elements, and availability of an independent pilot channel for directional comparison backup schemes.
Keywords :
power transmission protection; 87L protection schemes; asymmetrical channels; backup considerations; cables selective protection; directional comparison backup schemes; external time sources; forced line outages; independent pilot channel availability; line current differential protection; line protection redundancy; overcurrent elements; overhead lines protection; protection dependability; protection security; regulatory constraints; time backup strategies; Availability; Circuit faults; Circuit stability; Power system stability; Redundancy; Relays; Stability criteria;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2012 65th Annual Conference for
Conference_Location :
College Station, TX
Print_ISBN :
978-1-4673-1840-2
Type :
conf
DOI :
10.1109/CPRE.2012.6201224
Filename :
6201224
Link To Document :
بازگشت