• DocumentCode
    2107622
  • Title

    Asymmetrical operation of corridor with one single line

  • Author

    Sana, Abdou-R ; McGillis, D. ; Marccau, R.J. ; Do, X. Dai ; Olivier, Guy

  • Author_Institution
    Ecole Polytech., Montreal, Que., Canada
  • Volume
    2
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    936
  • Abstract
    In this paper, it is shown that it is possible to operate a three-phase line with one phase open on a permanent basis, without altering the integrity of the system. This is known as asymmetrical operation (AO) of transmission systems. A compensation scheme for eliminating the zero and the negative-sequence currents resulting from the asymmetrical operation of a system of one line is presented. A practical example is presented showing the amount of series and shunt compensation required to operate one line in asymmetrical mode
  • Keywords
    compensation; power transmission lines; asymmetrical operation; compensation scheme; negative-sequence currents elimination; one open phase; series compensation; shunt compensation; three-phase line; transmission systems; Capacitors; Circuit analysis; Joining processes; Linear circuits; Power filters; Power systems; Power transmission lines; Reactive power; Steady-state; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Computer Engineering, 2000 Canadian Conference on
  • Conference_Location
    Halifax, NS
  • ISSN
    0840-7789
  • Print_ISBN
    0-7803-5957-7
  • Type

    conf

  • DOI
    10.1109/CCECE.2000.849603
  • Filename
    849603