• DocumentCode
    2109782
  • Title

    Experimental Study of High-Pressure Fogging Cooling System in World Expo Axis

  • Author

    Lin Zhi-fen ; Zhao Hui-zhong ; Huang Chen ; Ye Da-fa ; Wu Ling-hong ; Liang Tao

  • Author_Institution
    Sch. of Environ. & Archit., Univ. of Shanghai for Sci. & Technol., Shanghai, China
  • fYear
    2010
  • fDate
    28-31 March 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper presents an experimental study of cooling effectiveness of the designed high-pressure fogging system in the World Expo axis. Eligible meteorological condition of air temperature is upon 30°C and its humidity is below 70% and different pressures of the pump were conducted in the experiment. The experimental results shows the high-pressure fogging system has a positive cool effect in the Expo axis, as a result of 2-3°C temperature descent and about 10% humidity ascend. Under fogging pressures of 7 MPa, 5 MPa, 3 MPa, the temperature descent is respectively 4.7°C, 3.6°C and 3.2°C, and relative humidity raise in 20.7%, 12.2% and 14.3%, furthermore, the black bulb temperature correspondingly drop 4.61°C, 4.1°C, 2.35°C at the distance of 1 m from the fogging pole.
  • Keywords
    cooling; meteorology; World Expo axis; black bulb temperature; high-pressure fogging cooling system; meteorological condition; pump; Acceleration; Cooling; Educational programs; Educational technology; Electronic mail; Humidity; Meteorology; Paper technology; Spraying; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-4812-8
  • Electronic_ISBN
    978-1-4244-4813-5
  • Type

    conf

  • DOI
    10.1109/APPEEC.2010.5449094
  • Filename
    5449094