DocumentCode
2110297
Title
Robustness of Distance Relay with Mho Characteristic against Inter Phase Faults Resistance
Author
Shateri, H. ; Jamali, S.
Author_Institution
Center of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran
fYear
2008
fDate
17-20 April 2008
Firstpage
1
Lastpage
6
Abstract
This paper discusses the maximum fault resistance, which can be tolerated by a distance relay with Mho characteristic in the case of inter phase, phase to phase and three phase, faults. This is defined as the boundary fault resistance, that in the case of the lower fault resistances, the relay can discriminate between in-zone and out-of-zone faults satisfactorily. The robustness criterion is defined based on the boundary fault resistance. In order to achieve this objective, the related equations are derived and then the boundary fault resistance curve and the robustness criterion are presented.
Keywords
fault diagnosis; relay protection; relays; boundary fault resistance curves; distance relay robustness; interphase fault resistance; robustness criterion; Circuit faults; Electrical resistance measurement; Frequency; Impedance measurement; Power system faults; Power system relaying; Power transmission lines; Protective relaying; Relays; Robustness;
fLanguage
English
Publisher
ieee
Conference_Titel
Region 5 Conference, 2008 IEEE
Conference_Location
Kansas City, MO
Print_ISBN
978-1-4244-2076-6
Electronic_ISBN
978-1-4244-2077-3
Type
conf
DOI
10.1109/TPSD.2008.4562745