DocumentCode
2110326
Title
Distance Relay Mal-Operation due to Presence of SSSC on Adjacent Lines in Inter Phase Faults
Author
Kazemi, A. ; Jamali, S. ; Shateri, H.
Author_Institution
Center of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran
fYear
2008
fDate
17-20 April 2008
Firstpage
1
Lastpage
6
Abstract
Thh paper discusses a distance relay mal-operation in the presence of Static Synchronous Series Compensator (SSSC), one of the series connected Flexible Alternating Current Transmission System (FACTS) devices, in the case of inter phase, phase to phase and three phase, faults. This is done by presenting the measured impedance at the relaying point in the presence of SSSC at the near end of the line behind. The measured impedance is greatly influenced in the presence of SSSC on the line or even in the case of SSSC installation on the adjacent lines, near end of the line behind. The measured impedance at the relaying point depends on many factors including the power system structural conditions, pre-fault loading, the fault resistance, and SSSC structural and controlling parameters.
Keywords
electric impedance measurement; flexible AC transmission systems; installation; power system relaying; power transmission faults; power transmission lines; power transmission protection; relay protection; static VAr compensators; FACTS device; SSSC installation; distance relay mal-operation; flexible alternating current transmission system; impedance measurement; inter phase fault; static synchronous series compensator; Control systems; Electrical resistance measurement; Flexible AC transmission systems; Impedance measurement; Power measurement; Power system faults; Power system measurements; Power system relaying; Protective relaying; Relays;
fLanguage
English
Publisher
ieee
Conference_Titel
Region 5 Conference, 2008 IEEE
Conference_Location
Kansas City, MO
Print_ISBN
978-1-4244-2076-6
Electronic_ISBN
978-1-4244-2077-3
Type
conf
DOI
10.1109/TPSD.2008.4562747
Filename
4562747