Title :
Distance Relay Mal-Operation due to Presence of SSSC on Adjacent Lines in Inter Phase Faults
Author :
Kazemi, A. ; Jamali, S. ; Shateri, H.
Author_Institution :
Center of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran
Abstract :
Thh paper discusses a distance relay mal-operation in the presence of Static Synchronous Series Compensator (SSSC), one of the series connected Flexible Alternating Current Transmission System (FACTS) devices, in the case of inter phase, phase to phase and three phase, faults. This is done by presenting the measured impedance at the relaying point in the presence of SSSC at the near end of the line behind. The measured impedance is greatly influenced in the presence of SSSC on the line or even in the case of SSSC installation on the adjacent lines, near end of the line behind. The measured impedance at the relaying point depends on many factors including the power system structural conditions, pre-fault loading, the fault resistance, and SSSC structural and controlling parameters.
Keywords :
electric impedance measurement; flexible AC transmission systems; installation; power system relaying; power transmission faults; power transmission lines; power transmission protection; relay protection; static VAr compensators; FACTS device; SSSC installation; distance relay mal-operation; flexible alternating current transmission system; impedance measurement; inter phase fault; static synchronous series compensator; Control systems; Electrical resistance measurement; Flexible AC transmission systems; Impedance measurement; Power measurement; Power system faults; Power system measurements; Power system relaying; Protective relaying; Relays;
Conference_Titel :
Region 5 Conference, 2008 IEEE
Conference_Location :
Kansas City, MO
Print_ISBN :
978-1-4244-2076-6
Electronic_ISBN :
978-1-4244-2077-3
DOI :
10.1109/TPSD.2008.4562747