DocumentCode
2111377
Title
Development of an on-line monitor to measure motor voltage surges
Author
Stone, G.C. ; Campbell, S.R.
Author_Institution
Iris Power Eng. Inc., Etobicoke, Ont., Canada
fYear
1997
fDate
22-25 Sep 1997
Firstpage
397
Lastpage
399
Abstract
Voltage surges from switchgear have long been known to lead to stator winding turn insulation failure in large form wound motors. With the widespread introduction of inverter fed drives (IFDs), it now appears that repetitive surges from the IFDs can lead to gradual deterioration and failure. An inexpensive monitor has been developed which continuously measures the risetime, magnitude and repetition rate of surges which strike a motor. In addition to measuring the basic risetime and magnitude data, the monitor also estimates the impact of the total surge history on the life of the insulation. Prototype testing of the system is extremely advanced
Keywords
computerised monitoring; insulation testing; life testing; machine insulation; motor drives; stators; surges; voltage measurement; insulation life; inverter fed drives; large form wound motors; motor voltage surges measurement; on-line monitor; prototype testing; repetitive surges; stator winding turn insulation failure; switchgear voltage surges; total surge history;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference, 1997, and Electrical Manufacturing & Coil Winding Conference. Proceedings
Conference_Location
Rosemont, IL
ISSN
0362-2479
Print_ISBN
0-7803-3959-2
Type
conf
DOI
10.1109/EEIC.1997.651162
Filename
651162
Link To Document