DocumentCode :
2114831
Title :
Study on Harmonic Losses of Inductive Filtering Converter Transformer (IFCT) in HVDC System
Author :
Yang, Dechang ; Li, Yong ; Rehtanz, Christian ; Luo, Longfu ; Xu, Jiazhu
Author_Institution :
Tech. Univ. Dortmund, Dortmund, Germany
fYear :
2010
fDate :
28-31 March 2010
Firstpage :
1
Lastpage :
4
Abstract :
Based on the wiring scheme and the operating principle of the inductive filtering converter transformer (IFCT), this paper analyzes the effect of harmonic on the converter transformer, and establishes the harmonic losses model for the traditional converter transformer (TCT) and the IFCT, respectively. Furthermore, according to the IEC61378-2 standard and the superposition principle, the harmonics losses are calculated in detail. The simulation results verify the correctness of the theoretical analysis, and show that the harmonic losses of the IFCT are lower than that of the TCT, and the implement of the inductive filtering method can reduce the losses of converter station greatly.
Keywords :
HVDC power convertors; power harmonic filters; power transformers; HVDC system; IEC61378-2 standard; harmonic losses model; inductive filtering converter transformer; traditional converter transformer; Active filters; Filtering; HVDC transmission; Harmonic analysis; Mathematical model; Passive filters; Power harmonic filters; Power system harmonics; Power transformers; Wiring;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
Conference_Location :
Chengdu
Print_ISBN :
978-1-4244-4812-8
Electronic_ISBN :
978-1-4244-4813-5
Type :
conf
DOI :
10.1109/APPEEC.2010.5449294
Filename :
5449294
Link To Document :