DocumentCode
2122721
Title
Maximum allowable penetration level determination of a DG in a distribution network
Author
Karimi-Zare, P. ; Seifi, H.
fYear
2012
fDate
9-12 Sept. 2012
Firstpage
355
Lastpage
360
Abstract
In steady state studies, the operation constraints such as bus voltages and lines currents are the main limiter factors for penetration of DGs in distribution networks. This paper proposes a method based on sensitivity of these constraints due to injection power in a specific bus. To determine the maximum allowable penetration level of an installed DG, the sensitivity analysis based on the linear model of the system is used. Also, the effects of network topology are evaluated on the allowable penetration level of the DG. This method is employed on the 69-bus test system. The impact of network operation modes on the DG penetration is also presented and evaluated.
Keywords
distributed power generation; distribution networks; sensitivity analysis; DG penetration; distributed power generation; distribution network; linear model; maximum allowable penetration level determination; network operation modes; network topology; sensitivity analysis; test system; Analytical models; Jacobian matrices; Load flow; Reactive power; Sensitivity analysis; Steady-state; DG; Penetration level; operation constraints; sensitivity analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Energy Conference and Exhibition (ENERGYCON), 2012 IEEE International
Conference_Location
Florence
Print_ISBN
978-1-4673-1453-4
Type
conf
DOI
10.1109/EnergyCon.2012.6347783
Filename
6347783
Link To Document