DocumentCode :
2128017
Title :
Experimental validation of a thermal model for the ampacity derating of electric cables in wrapped trays
Author :
de Cassia A.Figueiredo, R. ; Carneiro, Sandoval, Jr. ; Cruz, Manuel Ernani C
Author_Institution :
Furnas Centrais Eletricas SA, Rio de Janeiro, Brazil
fYear :
1997
fDate :
22-25 Sep 1997
Firstpage :
575
Lastpage :
582
Abstract :
As a safety measure for certain applications in nuclear power stations, cable trays must be wrapped with a fireproof material. In this paper a new implementation of a thermal model is presented, suitable for the determination of the ampacity derating of electric cables in covered trays. Model simulation predictions have been compared with field tests to validate the model. Better agreement between simulations and experimental results is obtained when the standard procedure to determine the power loss in the cable mass is modified to account for the actual measured height of the cable mass in the tray
Keywords :
electric conduits; flameproofing; nuclear power stations; power cables; safety; thermal analysis; ampacity derating; cable mass height; covered trays; electric cables; field tests; fireproof material; power loss determination; standard procedure; thermal model; wrapped trays;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference, 1997, and Electrical Manufacturing & Coil Winding Conference. Proceedings
Conference_Location :
Rosemont, IL
ISSN :
0362-2479
Print_ISBN :
0-7803-3959-2
Type :
conf
DOI :
10.1109/EEIC.1997.651254
Filename :
651254
Link To Document :
بازگشت