    NRC-PTB intercomparison of voltage transformer calibration systems for high voltage

  • Author

    So, E. ; Latzel, H.-G.

  • Author_Institution
    Inst. for Nat. Meas. Stand., Nat. Res. Council of Canada, Ottawa, Ont., Canada
  • fYear
    2000
  • fDate
    14-19 May 2000
  • Firstpage
    329
  • Lastpage
    330
  • Abstract
    An intercomparison of voltage transformer calibration systems was performed at the PTB high voltage laboratory. A "portable" current-comparator-based voltage transformer calibration system of NRC was compared with PTB\´s voltage-divider-based system, using a reference multi-ratio inductive voltage transformer with voltage ratios up to (400 kV//spl radic/3)/(100 V//spl radic/3) as a transfer standard. At frequencies of 50 Hz and 60 Hz with a resistive burden of 10 k/spl Omega/ and test voltages of 20% up to 120% of rated voltage, the test results of the two different methods at all ratios were found to differ by no more than 15/spl times/10/sup -6/ for the voltage ratio and 30 /spl mu/rad for the phase displacement.
  • Keywords
    calibration; current comparators; high-voltage techniques; measurement standards; potential transformers; voltage dividers; voltage measurement; 10 kohm; 50 Hz; 60 Hz; NRC-PTB intercomparison; cascade-type design; high voltage; phase displacement; portable current-comparator-based; reference multi-ratio inductive voltage transformer; transfer standard; voltage ratio; voltage transformer calibration systems; voltage-divider-based system; Bridge circuits; Calibration; Capacitors; Councils; Low voltage; Measurement standards; Performance evaluation; Phase measurement; Testing; Voltage transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements Digest, 2000 Conference on
  • Conference_Location
    Sydney, NSW, Australia
  • Print_ISBN
    0-7803-5744-2
  • Type

    conf

  • DOI
    10.1109/CPEM.2000.851010
  • Filename
    851010