Short-line fault interruption capability of vacuum circuit breakers
Author :
Smeets, R.P.P. ; van der Linden, W.A.
Author_Institution :
KEMA High-Power Lab., Arnhem, Netherlands
fYear :
2002
fDate :
2002
Firstpage :
34
Lastpage :
37
Abstract :
Current zero measurements are performed during short-line fault interruption tests of vacuum circuit breakers. Various reignition modes (occurring between 0 and 75 ms after current zero) were observed due to insufficient arcing time. The (single) restrike and the (single) failure occurred with higher current than rated. The relationship between post-arc current/charge, reignition mode and TRV are discussed in this paper. All interrupters succeeded to interrupt at first or second current zero under the ´rated´ conditions of short-line fault current and TRV.
Keywords :
circuit-breaking arcs; power system faults; switchgear testing; vacuum circuit breakers; vacuum interrupters; 0 to 75 ms; arcing time; current zero measurements; reignition modes; short-line fault interruption capability; transient recovery voltages; vacuum circuit breakers; Circuit breakers; Circuit faults; Circuit testing; Current measurement; Fault currents; Instrument transformers; Interrupters; Laboratories; Performance evaluation; Voltage;