• DocumentCode
    2147043
  • Title

    Analysis on dynamic dielectric recovery and statistical property of vacuum circuit-breakers with multi-breaks

  • Author

    Min-fu, Liao ; Ji-yan, Zou ; Xiong-ying, Duan

  • Author_Institution
    Dept. of Electr. & Electron. Eng., Dalian Univ. of Technol., China
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    602
  • Lastpage
    605
  • Abstract
    Based on the analysis of dynamic dielectric recovery process on vacuum gaps in series, investigations were made on vacuum circuit breakers with double and multi-breaks. From the research on the breakdown weak points in high field vacuum gaps, their turn out and distribution, a theoretic model was set up for describing the statistical property of multi-breaks vacuum circuit-breakers, that can explain the mechanism on the improvement of breaking capacity for multi-breaks units compared with single-break ones which have the same equivalent gap length.
  • Keywords
    dielectric properties; statistical analysis; vacuum circuit breakers; double-break vacuum circuit breakers; dynamic dielectric recovery; equivalent gap length; high field vacuum gaps; multi-break vacuum circuit breakers; series vacuum gaps; statistical property; Circuit breakers; Circuit testing; Dielectrics and electrical insulation; Interrupters; Power system dynamics; RLC circuits; Transient analysis; Vacuum breakdown; Vacuum technology; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum, 2002. 20th International Symposium on
  • Print_ISBN
    0-7803-7394-4
  • Type

    conf

  • DOI
    10.1109/ISDEIV.2002.1027444
  • Filename
    1027444