DocumentCode
2151784
Title
The influence of the arc voltage in synthetic test circuits
Author
van der Sluis, L. ; Sheng, B.L.
Author_Institution
Power Syst. Lab., Delft Univ. of Technol., Netherlands
fYear
1994
fDate
10-15 Apr 1994
Firstpage
143
Lastpage
148
Abstract
In this paper, different arc voltage waveforms and KEMA arc models are used to study the stress of the direct SLF ( short line fault) test circuit and the synthetic SLF test circuit on the TB (test breaker). For the synthetic test circuit the total arc energy input in the TB is less than in the direct test circuit, but just before the current zero, the dI/dt and subsequently the arc energy input in the TB is higher. It is demonstrated that the arc-circuit interaction plays an important role for the TB to clear the fault. For SF6 circuit breakers with an arc voltage of significant extinguishing peak, the voltage injection synthetic test circuit produces an overstress for the TB
Keywords
arcs (electric); circuit breakers; circuit-breaking arcs; high-voltage techniques; switchgear testing; KEMA arc models; SF6 circuit breakers; arc voltage; arc voltage waveforms; short line fault test circuit; synthetic test circuits; total arc energy input; voltage injection synthetic test circuit; Circuit breakers; Circuit faults; Circuit testing; Laboratories; Power system faults; Power system modeling; Short circuit currents; Stress; System testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1994., Proceedings of the 1994 IEEE Power Engineering Society
Conference_Location
Chicago, IL
Print_ISBN
0-7803-1883-8
Type
conf
DOI
10.1109/TDC.1994.328373
Filename
328373
Link To Document