  • Abstract
    In this paper, different arc voltage waveforms and KEMA arc models are used to study the stress of the direct SLF ( short line fault) test circuit and the synthetic SLF test circuit on the TB (test breaker). For the synthetic test circuit the total arc energy input in the TB is less than in the direct test circuit, but just before the current zero, the dI/dt and subsequently the arc energy input in the TB is higher. It is demonstrated that the arc-circuit interaction plays an important role for the TB to clear the fault. For SF6 circuit breakers with an arc voltage of significant extinguishing peak, the voltage injection synthetic test circuit produces an overstress for the TB
  • Keywords
    arcs (electric); circuit breakers; circuit-breaking arcs; high-voltage techniques; switchgear testing; KEMA arc models; SF6 circuit breakers; arc voltage; arc voltage waveforms; short line fault test circuit; synthetic test circuits; total arc energy input; voltage injection synthetic test circuit; Circuit breakers; Circuit faults; Circuit testing; Laboratories; Power system faults; Power system modeling; Short circuit currents; Stress; System testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1994., Proceedings of the 1994 IEEE Power Engineering Society
  • Conference_Location
    Chicago, IL
  • Print_ISBN
    0-7803-1883-8
  • Type

    conf

  • DOI
    10.1109/TDC.1994.328373
  • Filename
    328373