Ampacity calculations for mixed underground cable systems in the same ductbank
Author
Kansog, Jurgen O C ; Brown, Matthew T.
Author_Institution
Ebasco Div., Raytheon Eng. & Constructors, Lyndhurst, NJ, USA
fYear
1994
fDate
10-15 Apr 1994
Firstpage
535
Lastpage
543
Abstract
The steady state ampacity is calculated for mixed electric power underground cable circuits in a single trench or ductbank. The methodology presented in this paper can be applied to any practical number of balanced, three phase circuits (each in trefoil, pipe or conduit) of different voltage classes, cable sizes, load currents and cable systems located anywhere within a single trench or ductbank. The different thermal resistivities of the backfill or ductbank and the surrounding soil are taken into consideration. A practical example for 10 circuits in a trench is provided
Keywords
electric conduits; power cables; soil; thermal conductivity; underground cables; backfill; cable size; conduit; ductbank; load current; mixed power underground cable circuits; pipe; soil; steady state ampacity; thermal resistivity; three phase; trefoil; trench; voltage class; Cables; Circuits; Conductivity; Conductors; Interference; Soil; Steady-state; Temperature; Thermal loading; Thermal resistance;