• DocumentCode
    2153646
  • Title

    Neutral reactors on shunt compensated EHV lines

  • Author

    Atmuri, S.R. ; Thallam, R.S. ; Gerlach, D.W. ; Lundquist, T.G. ; Selin, D.A.

  • Author_Institution
    Teshmont Consultants Inc., Winnipeg, Man., Canada
  • fYear
    1994
  • fDate
    10-15 Apr 1994
  • Firstpage
    121
  • Lastpage
    128
  • Abstract
    This paper examines the applications of a neutral reactor in limiting resonance overvoltages induced on deenergized conductors due to parallel energized circuits and stuck breaker conditions. These applications are demonstrated through the planned 243 mile long Mead-Phoenix 500 kV line running on the same right of way as the existing Mead-Liberty 345 kV line. Reducing the secondary arc current during single pole reclosing is also examined. In addition to its applications, a procedure for sizing, rating and protection of the neutral reactor is explained
  • Keywords
    circuit breakers; compensation; overvoltage protection; power transmission lines; reactors (electric); resonance; 243 mile; 345 kV; 500 kV; Mead-Liberty 345 kV line; Mead-Phoenix 500 kV line; deenergized conductors; neutral reactors; parallel energized circuits; resonance overvoltages limiting; secondary arc current; shunt compensated EHV lines; single pole reclosing; stuck breaker conditions; Capacitance; Conductors; Inductors; RLC circuits; Resonance; Rivers; Shunt (electrical); Surges; Transmission lines; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1994., Proceedings of the 1994 IEEE Power Engineering Society
  • Conference_Location
    Chicago, IL
  • Print_ISBN
    0-7803-1883-8
  • Type

    conf

  • DOI
    10.1109/TDC.1994.328443
  • Filename
    328443