Title :
Neutral reactors on shunt compensated EHV lines
Author :
Atmuri, S.R. ; Thallam, R.S. ; Gerlach, D.W. ; Lundquist, T.G. ; Selin, D.A.
Author_Institution :
Teshmont Consultants Inc., Winnipeg, Man., Canada
Abstract :
This paper examines the applications of a neutral reactor in limiting resonance overvoltages induced on deenergized conductors due to parallel energized circuits and stuck breaker conditions. These applications are demonstrated through the planned 243 mile long Mead-Phoenix 500 kV line running on the same right of way as the existing Mead-Liberty 345 kV line. Reducing the secondary arc current during single pole reclosing is also examined. In addition to its applications, a procedure for sizing, rating and protection of the neutral reactor is explained
Keywords :
circuit breakers; compensation; overvoltage protection; power transmission lines; reactors (electric); resonance; 243 mile; 345 kV; 500 kV; Mead-Liberty 345 kV line; Mead-Phoenix 500 kV line; deenergized conductors; neutral reactors; parallel energized circuits; resonance overvoltages limiting; secondary arc current; shunt compensated EHV lines; single pole reclosing; stuck breaker conditions; Capacitance; Conductors; Inductors; RLC circuits; Resonance; Rivers; Shunt (electrical); Surges; Transmission lines; Voltage;
Conference_Titel :
Transmission and Distribution Conference, 1994., Proceedings of the 1994 IEEE Power Engineering Society
Conference_Location :
Chicago, IL
Print_ISBN :
0-7803-1883-8
DOI :
10.1109/TDC.1994.328443